Σωλήνες Χαλκού

TALOSⓇ ACR LINESETS

Συστήματα κλιματισμού και Αντλιών θερμότητας

TALOS ACR Linesets are designed especially for the split Air-Conditioning and Heat Pump Systems products requiring installation with flared connections. The unique advantages offered by TALOS ACR Linesets, including, copper resistance and durability, high performance foam insulation and pre-flared ends with mounted flare nuts, result in significant energy savings and in quick, cost effective field installations.

Copper Tube Material

Copper phosphorus deoxidised (DHP-Cu) with min. copper

content 99,90% and P=0,015% – 0,040%.

Specifications

REFRIGERATION PIPES: EN 12735-1

FOAM INSULATION: EN 13501-1

FLARE FITTINGS: SAE J513.

Quality Marks

REFRIGERATION PIPES: AENOR, TÜV, GL.

Instructions

Follow the equipment manufacturer’s installation instructions regarding refrigerant tubing, system evacuation and testing for leaks.

  • Remove protective shipping plugs.
  • Properly connect and tighten the flare nut to the approved level of torque.
  • Take precautions not to crimp tube when bending.
  • Take precautions not to tear the insulation.
  • Do not allow contaminants to be introduced inside the network.

Mechanical Properties

TemperEN 12735 ClassificationMinimum Tensile strength Rm (MPa)Min elongation, A%
SoftR-22022040

Standard Dimensions

COPPER TUBE EXTERNAL DIAMETER INCHCOPPER TUBE EXTERNAL DIAMETER MMCOPPER TUBE WALL THICKNESS MMOVERALL EXTERNAL DIAMETER WITH 9MM THICK INSULATION MM
3/164,760,8022,76
1/46,350,8024,35
5/167,940,8025,94
3/89,520,8025,72
1/212,700,8030,70
5/815,871,0033,87
3/419,051,0037,05
7/822,231,0040,23

Standard Pair Dimensions

COPPER TUBE EXTERNAL DIAMETER INCHCOPPER TUBE EXTERNAL DIAMETER MMCOPPER TUBE WALL THICKNESS MMOVERALL EXTERNAL DIAMETER WITH 9MM THICK INSULATION MM
¼-3 / 86,35-9,520,80-0,8024,4-27,5
¼-1 / 26,35-12,70,80-0,8024,4-30,7
¼-5 / 86,35-15,880,80-1,0024,4-33,9
¼-3 / 46,35-19,050,80-1,0024,4-37,10
3 / 8-1 / 29,52-12,70,80-0,8027,5-30,7
3 / 8-5 / 89,52-15,880,80-1,0027,5-33,9
3 / 8-3 / 49,52-19,050,80-1,0027,5-37,1
½-3 / 412,7-19,050,80-1,0030,7-37,1

Other sizes and special packaging in pallets or cardboard boxes are available upon request.

Insulation Technical Properties

MATERIALPE-X foam
DENSITY ACCORDING TO DIN 53420 ASTM D 166730-33 Kg/m3
THERMAL CONDUCTIVITY COEFFICIENT (λ) ACCORDING TO ASTM C 3350,039 W/m.K  
VAPOUR-WATER DIFFUSSION RESISTANCE COEFFICIENT (μ) ACCORDING TO ISO 12572> 9.000  
WORKING TEMPERATURE-80oC to +110oC
FIRE RESISTANCEEN 13501–1, Class B or Class E, DIN 4102, B2, BS 476, NF P 92 501-M1
RESISTANCE TO CHEMICAL AGENTS ACC. TO ASTM 543-56 TVery good
SOUND ABSORPTION ACC. TO DIN 4109 300-2500Hz~60%
DIMENSIONAL STABILITY ACCORDING TO ISO 2796 FOR TEMPERATURES UP TO 1000C<5%

Values are listed, as obtained under standard laboratory conditions and may be amended, without prior notice.