Kupferrohre
TALOSⓇ ACR ECUTHERM II™
Kälte, Klima
Copper Tube Material
Copper phosphorus deoxidised (DHP-Cu), having minimum copper content 99,90% and P=0,015% – 0,040%.
Quality Marks
REFRIGERATION PIPES: ΑΕΝΟR TÜV, GL, VIK.

Mechanical Properties
Temper | EN 12735 Classification | Minimum Tensile strength Rm (MPa) | Min elongation, A% |
---|---|---|---|
Soft | R-220 | 220 | 40 |
Insulation Technical Properties
MATERIAL | PE-X or PE foam |
DENSITY ACCORDING TO DIN 53420 ASTM D 1667 | 30-33 Kg/m3 |
THERMAL CONDUCTIVITY COEFFICIENT (λ) ACCORDING TO EN ISO 8497 | 0.0357 W/mK (0oC)0,0389 W/mK (40oC) |
VAPOUR-WATER DIFFUSSION RESISTANCE COEFFICIENT (μ) ACCORDING TO EN 13469 | 12.500 |
WORKING TEMPERATURE | -80oC to +110oC(+90oC for PE foam) |
FIRE RESISTANCE | EN 13501–1, Class B or Class E, DIN 4102, B2, BS 476, NF P 92 501-M1 |
RESISTANCE TO CHEMICAL AGENTS ACC. TO ASTM 543-56 T | Very good |
DIMENSIONAL STABILITY ACCORDING TO ISO 2796 FOR TEMPERATURES UP TO 1000C | <5% |
Values are listed, as obtained under standard laboratory conditions and may be amended, without prior notice.
Standard Pair Dimensions (Coils 15m, 25m, 30m Long)
COPPER TUBE EXTERNAL DIAMETER INCH | COPPER TUBE EXTERNAL DIAMETER MM | COPPER TUBE WALL THICKNESS MM | OVERALL EXTERNAL DIAMETER WITH 9MM THICK INSULATION MM |
---|---|---|---|
¼-3/8 | 6,35-9,52 | 0,80-0,80 | 24,4-27,5 |
¼-1/2 | 6,35-12,7 | 0,80-0,80 | 24,4-30,7 |
¼-5/8 | 6,35-15,88 | 0,80-1,00 | 24,4-33,9 |
¼-3/4 | 6,35-19,05 | 0,80-1,00 | 24,4-37,10 |
3/8-1/2 | 9,52-12,7 | 0,80-0,80 | 27,5-30,7 |
3/8-5/8 | 9,52-15,88 | 0,80-1,00 | 27,5-33,9 |
3/8-3/4 | 9,52-19,05 | 0,80-1,00 | 27,5-37,1 |
½-3/4 | 12,7-19,05 | 0,80-1,00 | 30,7-37,1 |
Other sizes and special packaging in pallets or cardboard boxes are available upon request.
Pair Diameters
1/4″ + 3/8″
1/4″ + 1/2″
1/4″ + 5/8″
1/4″ + 3/4″
3/8″ + 1/2″
3/8″ + 5/8″
3/8″ + 3/4″
1/2″ + 3/4″
Appropriate also for the new Green Refrigeration Units
According to the European Standard EN12735-1:2010, as well as current market requirements, laid down by the use of new generation of refrigerants, including HFCs and HFOs, adopted by all major manufacturers of refrigeration and air conditioning units the following standardisation is applied to TALOSⓇ ACR ECUTHERM 2TM copper tubes:
- For an external diameter of 1/4” to 1/2”, the wall thickness is standardised at 0,80 mm