TALOS® ACR Linesets

Applications

Air conditioning and heat pump systems

TALOS® ACR Linesets are designed especially for the splitAir-Conditioning and Heat Pump Systems products requiringinstallation with flared connections. The unique advantagesoffered by TALOS® ACR Linesets, including, copper resistanceand durability, high performance foam insulation andpre-flared ends with mounted flare nuts, result in significantenergy savings and in quick, cost effective field installations.

 

 

Copper Tube Material

Copper phosphorus deoxidised (DHP-Cu) with min. copper

content 99,90% and P=0,015% - 0,040%.

Specifications

REFRIGERATION PIPES: EN 12735-1

FOAM INSULATION: EN 13501-1

FLARE FITTINGS: SAE J513.

Quality Marks

REFRIGERATION PIPES: AENOR, TÜV, GL NSF.

Instructions

Follow the equipment manufacturer’s installation instructionsregarding refrigerant tubing, system evacuation and testingfor leaks.

  • Remove protective shipping plugs.
  • Properly connect and tighten the flare nut to the approvedlevel of torque.
  • Take precautions not to crimp tube when bending.
  • Take precautions not to tear the insulation.
  • Do not allow contaminants to be introduced inside thenetwork.

 

Mechanical Properties

Temper EN 12735 
Classification
Minimum Tensile strength 
Ν/mm2
Minimum elongation
Α%

Soft

R-220

220

40

 

Standard Dimensions according to EN 12735-1

Copper tube external diameter

Inch 

3/16

1/4

5/16

3/8

1/2

5/8

3/4

7/8

mm

4,76

6,35

7,94

9,52

12,70

15,87

19,05

22,23

Copper tube wall thickness

mm

0,80

0,80

0,80

0,80

0,80

1,00

1,00

1,00

Overall external diameter with 9mm thick insulation

mm

22,76

24,35

25,94

25,72

30,70

33,87

37,05

40,23

 

Standard Pair Dimensions (Coils 2-15m)

Copper tube external diameter

Inch 

¼-3/8

¼-1/2

¼-5/8

¼-3/4

3/8-1/2

3/8-5/8

3/8-3/4

½-3/4

mm

6,35-9,52

6,35-12,7

6,35-15,88

6,35-19,05

9,52-12,7

9,52-15,88

9,52-19,05

12,7-19,05

Copper tube wall thickness

mm

0,80-0,80

0,80-0,80

0,80-1,00

0,80-1,00

0,80-0,80

0,80-1,00

0,80-1,00

0,80-1,00

Overall external diameter with 9mm thick insulation

mm

24,4-27,5

24,4-30,7

24,4-33,9

24,4-37,10

27,5-30,7

27,5-33,9

27,5-37,1

30,7-37,1

Other sizes and special packaging in pallets or cardboard boxes are available upon request.

Insulation Technical Properties

MATERIAL

PE-X foam

DENSITY ACCORDING TO DIN 53420 ASTM D 1667

30-33 Kg/m3

THERMAL CONDUCTIVITY COEFFICIENT (λ)

ACCORDING TO ASTM C 335

0,039W/m.K

 

VAPOUR-WATER DIFFUSSION RESISTANCE

COEFFICIENT (μ) ACCORDING TO ISO 12572

> 9.000

 

WORKING TEMPERATURE

-80oC to +110oC

FIRE RESISTANCE

EN 13501–1, Class B or Class E, DIN 4102, B2, BS 476, NF P 92 501-M1

RESISTANCE TO CHEMICAL AGENTS ACC. TO ASTM 543-56 T

Very good

SOUND ABSORPTION ACC. TO DIN 4109 300-2500Hz

~60%

DIMENSIONAL STABILITY ACCORDING TO ISO 2796 FOR TEMPERATURES UP TO 100 0C

<5%

Values are listed, as obtained under standard laboratory conditions and may be amended, without prior notice.