Refrigeration and air conditioning

Copper Tube Material

Copper phosphorus deoxidised (Cu-DHP) with min. copper content 99,90% and Ρ=0,015% - 0,040%.

 

 

 

Specifications

REFRIGERATION PIPES: EN 12735-1.

Quality Marks

REFRIGERATION PIPES: AENOR, TÜV, GL, VIK.

 

Mechanical Properties

Temper
EN 12735
Classification
Min. Tensile Strength, Rm (MPa)
Min elongation
Α (%)

Soft

R-220

220

40

 

Insulation Technical Properties

MATERIAL

PE-X or PE foam

DENSITY ACCORDING TO DIN 53420 ASTM D 1667

30-33 Kg/m3

THERMAL CONDUCTIVITY COEFFICIENT (λ)

ACCORDING TO ASTM C 335

0,039W/m.K

 

VAPOUR-WATER DIFFUSSION RESISTANCE

COEFFICIENT (μ) ACCORDING TO ISO 12572

> 9.000

 

WORKING TEMPERATURE

-80oC to +110oC (+90oC for PE foam)

FIRE RESISTANCE

EN 13501–1, Class B or Class E, DIN 4102, B2, BS 476, NF P 92 501-M1

RESISTANCE TO CHEMICAL AGENTS ACC. TO ASTM 543-56 T

Very good

SOUND ABSORPTION ACC. TO DIN 4109 300-2500Hz

~60%

DIMENSIONAL STABILITY ACCORDING TO ISO 2796 FOR TEMPERATURES UP TO 100 0C

<5%

Values are listed, as obtained under standard laboratory conditions and may be amended, without prior notice.

 

TALOS ACR ECUTHERM™ Standard Dimensions according to EN 12735-1

Copper tube external diameter

Inch 

3/16

1/4

5/16

3/8

1/2

5/8

3/4

7/8

mm

4,76

6,35

7,94

9,52

12,70

15,87

19,05

22,23

Copper tube wall thickness

mm

0,80

0,80

0,80

0,80

0,80

1,00

1,00

1,00

Overall external diameter with 9mm thick insulation

mm

22,76

24,35

25,94

25,72

30,70

33,87

37,05

40,23

The values of the permissible operating pressure are calculated with a safety factor 4according to AD2000-Merkblatt B0/B1 for R220 (soft) condition and temperature up to 100 ⁰C.